BDA Directory List

Product Title: SHIELD SOLO
Supported Bands: 700, 800, 700/800 Dual-Band
Class: A
Uplink Frequencies in MHz: From: 798 MHz To: 816 MHz
Downlink Frequencies in MHz: From: 768 MHz To: 861 MHz
Uplink Composite Power in dBm: 30
Downlink Composite Power in dBm: 30
Power Consumption (Input Power): 65
2524 Listing Status: Listed
2524 NRTL for Listed Products: INTERTEK/ETL
2524 Certification Date: Tuesday, May 10, 2022
STD 2524 Certification Image: View Certificate
STD 2524 Comments:
Other Certifications:
Website: CEL-FI SOLO
Notes: Class A/B software selectable unit that can be converted in the field without additional codes or license fees. Class A: 64 Channels at 12.5 kHz. Class B: 56 Channels at 100 kHz or 150 kHz.


Product Title: TruePath - Channelized (Class A) 700 or 800 MHz Public Safety BDA, 1/2 Watt, DC
Supported Bands: 700, 800, Band 14
Class: A
Uplink Frequencies in MHz: From: 788 MHz To: 824 MHz
Downlink Frequencies in MHz: From: 758 MHz To: 896 MHz
Uplink Composite Power in dBm: 27
Downlink Composite Power in dBm: 27
Power Consumption (Input Power): 160
2524 Listing Status: Listed
2524 NRTL for Listed Products: UL
2524 Certification Date: Wednesday, May 31, 2023
STD 2524 Certification Image: View Certificate
STD 2524 Comments: Investigated to UL2524 - 2nd Edition Revised 2019-02-28, Bi-directional amplifier
Other Certifications: CAN/CSA-C22.2 No.62638-1 FCC Part 20 Part 90
Website: 7831758-0022
Notes: Wireless Supply also offers our BDA products as a kit which includes the BBU, annunciator, and alarm junction boxes for connection to a buildings fire alarm panel


Product Title: TruePath - Channelized (Class A) 700 or 800 MHz Public Safety BDA, 2 Watts, DC
Supported Bands: 700, 800, Band 14
Class: A
Uplink Frequencies in MHz: From: 788 MHz To: 824 MHz
Downlink Frequencies in MHz: From: 758 MHz To: 896 MHz
Uplink Composite Power in dBm: 27
Downlink Composite Power in dBm: 33
Power Consumption (Input Power): 160
2524 Listing Status: Listed
2524 NRTL for Listed Products: UL
2524 Certification Date: Wednesday, May 31, 2023
STD 2524 Certification Image: View Certificate
STD 2524 Comments: Investigated to UL2524 - 2nd Edition Revised 2019-02-28, Bi-directional amplifier
Other Certifications: CAN/CSA-C22.2 No. 62638-1, FCC Part 20 Part 90
Website: 7831758-002
Notes: Wireless Supply also offers our BDA products as a kit which includes the BBU, annunciator, and alarm panel junction boxes for connection to a buildings fire alarm panel


Product Title: TruePath - Channelized (Class A) 700 or 800 MHz Public Safety BDA, 2 Watts, AC
Supported Bands: 700, 800, Band 14
Class: A
Uplink Frequencies in MHz: From: 788 MHz To: 824 MHz
Downlink Frequencies in MHz: From: 758 MHz To: 896 MHz
Uplink Composite Power in dBm: 27
Downlink Composite Power in dBm: 33
Power Consumption (Input Power): 160
2524 Listing Status: Listed
2524 NRTL for Listed Products: UL
2524 Certification Date: Wednesday, May 31, 2023
STD 2524 Certification Image: View Certificate
STD 2524 Comments: Investigated to UL2524 - 2nd Edition Revised 2019-02-28, Bi-directional amplifier
Other Certifications: CAN/CSA-C22.2 No. 62638-1, FCC Part 20 Part 90
Website: 7831758-0001
Notes: Wireless Supply also offers our BDA products as a kit which includes the BBU, annunciator, and alarm junction boxes for connection to a buildings fire alarm panel


Product Title: TruePath - Channelized (class A) 700 or 800 MHz Public Safety BDA, 1/2 Watt, AC
Supported Bands: 700, 800, Band 14
Class: A
Uplink Frequencies in MHz: From: 788 MHz To: 824 MHz
Downlink Frequencies in MHz: From: 758 MHz To: 896 MHz
Uplink Composite Power in dBm: 27
Downlink Composite Power in dBm: 27
Power Consumption (Input Power): 160
2524 Listing Status: Listed
2524 NRTL for Listed Products: UL
2524 Certification Date: Wednesday, May 31, 2023
STD 2524 Certification Image: View Certificate
STD 2524 Comments: Investigated to UL2524 - 2nd Edition Revised 2019-02-28, Bi-directional amplifier
Other Certifications: CAN/CSA-C22-2 No. 62638-1, FCC Part 20 Part 90
Website: 7831758-0012
Notes: Wireless Supply also offers our BDA products as a kit which includes the BBU, annunciator and alarm junction boxes for connection to a buildings fire alarm panel


Product Title: ProtectLink Class A Software definable ERCES system
Supported Bands: 700, 800, 700/800 Dual-Band, Band 14
Class: A
Uplink Frequencies in MHz: From: 788 MHz To: 824 MHz
Downlink Frequencies in MHz: From: 758/851 MHz To: 776/869 MHz
Uplink Composite Power in dBm: 27
Downlink Composite Power in dBm: 34
Power Consumption (Input Power): 130
2524 Listing Status: Listed
2524 NRTL for Listed Products: INTERTEK/ETL
2524 Certification Date: Thursday, February 25, 2021
STD 2524 Certification Image: View Certificate
STD 2524 Comments: Systems consists of one ProtectLink BDA (available currently in 5 models) plus CS19-BBC-003 battery cabinet with UL Recognized sealed lead acid batteries and CS40-ANNUNC remote annunciation panel.
Other Certifications: UL 62368-1, Communications Technology Equipment. UL508A (UL50E NEMA Type 4). FCC ID NVRDPSA81090-78 Canada ISED 4307A-DPSA810907
Notes: Westell ProtectLink Public Safety BDAs represent the next revolution in DAS design, offering the most flexible platform available on the market. Available in 5 models, 2.5W or 1W, single or dual band.